Time Clock out of sequence on New MTU Gas MMC Controllers
There have been issues with the IPC touch screen on the MTU GAs engines in particular when a replacement touchscreen has been ordered from the factory.MTU OEG has informed that there is a windows function which synchronizes time with a timeserver, ...
ECS-UNI spare parts and replacement
Since a couple of years you can't get spares for ECS-UNI anymore. ECS-UNI (Main and Back-up) and ECS-UNI LOP will be replaced by ADEC-UNI (Main and Back-up) and ADEC-UNI LOP.The ECS-UNI and ECS-UNI LOP had the FSW software stored in on-board memory ...
Display Download Project Error - Error MTU.dll
Display Download Project Error Display DIS10-13 (DIS Firmware: DIS Loader 8.02) An error occurs when the new display downloads the application data from an external BDM server: the download occurs when the display downloads the project data. The DIS ...
MSP replacement- setting Engine hours correctly
If you can change the parametervalue for engine hours on the MSP, but the new value is not accepted: After you set the correct parametervalue, press two times only the button “SELECT” to get to the next parameter . Now to get out of the configuration ...
DDEC IV EDM connection recommendations and possible corruption with DDDL use
EDM (standard Detroit Electonic Display Module) as designed for he DDEC system is wired into the 900/901 can bus (which is J1587 data link) it can 'drop out' when DDDL (diagnostic tooling) is connected into the same link etc...our recommendations are ...